Non combustible testing furnace for building materials ISO1182 BS476-4
ISO 1182 : Reaction to fire tests for products -- Non-combustibility test
Introduction:
NCF ISO1182 BS476-6 Non-combustibility Tester is designed and manufactured in accordance with EN ISO1182 standard , it is mainly for building products testing.
NCF ISO1182 BS476-6 Non-combustibility Tester is mainly used in the non-combustibility test for building materials, and is suitable for classification of combustion performance of Class A fireproof materials.
NCF ISO1182 BS476-6 Non-combustibility Tester is suitable for both composite products and materials of the components testing.
NCF ISO1182 BS476-6 Non-combustibility Tester is also comply to BS 476-4 & 11 and IMO FTP Part 1 standards. So it can also test UK building materials, railway materials and non-metallic products of vessel.
Standards:
BS: BS 476-4
ISO: ISO 1182
EN: EN 13501
IMO: FTPC Part 1
Application Field:
Building Materials;
Rail;
IMO;
Features:
Non-Combustibility Furnace measures in-combustibility and combustibility of uniform building material and non-uniform building material of actual element.
The evaluations (results) are rising temperature in the furnace, basic mass loss and ignition of specimen.
Single Zone Furnace operable at up to 900 oC with the Kanthal Ribbon Heater.
750±5oC temperature automatically control by PID and Power controller.
Provided with stabilized voltage supply for more quick temperature stabilization.
Equipped with 3 thermocouples, for temperature in furnace, specimen center, and specimen surface respectively.
Testing results include:
Mass Loss(g) and Rate(%)
Ignition Time(s) and Sustained Flaming(s)
Initial & Maximum Furnace Temperature(oC)
Final Furnace Temperature(oC)
Maximum Specimen Center Temperature(oC)
Final Specimen Center Temperature(oC)
Furnace Temperature Rise(oC)
Specimen Center & Surface Temperature Rise(oC).